Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM05836
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/15/2019 | SAMUEL ROGERS | ZONING | REVIEW | Approved | |
08/15/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1.Coordinate the mechanical design shown on sheet M1 with the heating/cooling load calculations, the mechanical COMcheck, and sheet P1. 2. Provide the rational for determining the ventilation requirement for the workroom. Reference: Section 403.3.1.1, IMC 2018. |
08/15/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/15/2019 | SROGERS2 | ENGINEERING | REVIEW | Passed | |
08/15/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1; Roof Plan: Please provide structural calculations for the existing roof structure at the new heat pump (see Sheet M1). |
08/15/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/15/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Coordinate sheet P-1 (condensate drains) with the mechanical design. |
08/15/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/15/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |