Permit Number: T19CM05188
Parcel: 12709011P

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM05188
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The lighting com check must be calculated per the current 2018 IECC. See plan review comment #2, 8-29-19. Please revise.
Ref; 2018 IBC 107.2.1, 2018 IECC, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/21/2020 JWILLIA2 REJECT SHELF Completed
02/06/2020 SBORZAK1 OUT TO CUSTOMER Completed