Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM05188
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/27/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Plan Sheet E101 and E501… The Outdoor Lumen Calcs for each plan sheet do not correlate.. Remove the lumen calcs not desired to be part of the revised plan set. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/31/2020 | SBORZAK1 | REJECT SHELF | Completed |
| 01/27/2020 | SBORZAK1 | OUT TO CUSTOMER | Completed |