Permit Number: T19CM05188
Parcel: 12709011P

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM05188
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1 Per previous plan review comments to provide compliance with the Tucson/Pima County Outdoor Lighting Code section 104 (Plan Submission Requirements)… Provide a lighting site plan and show all the exterior lighting locations on the parcel. Identify each luminaire with a mark that correlates with the outdoor lighting calcs. (OLC) sec 104.2 (1).
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code, (OLC).
12/26/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved