Permit Number - T19CM05188
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/10/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1 Per previous plan review comments to provide compliance with the Tucson/Pima County Outdoor Lighting Code section 104 (Plan Submission Requirements)… Provide a lighting site plan and show all the exterior lighting locations on the parcel. Identify each luminaire with a mark that correlates with the outdoor lighting calcs. (OLC) sec 104.2 (1). Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code, (OLC). |
| 12/26/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |