Permit Number - T19CM05188
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. As requested per the previous electrical plan review comment. The lighting plan must provide evidence that the proposed exterior lighting complies with the requirements of the Tucson/Pima County Outdoor Lighting Code. See section 104 for plan submittal requirements. 2. Provide lumen calcs to show compliance with the lumens allowed per acre. See table 401.1. 3. Indicate the size of the parcel in arces, and the total allowable lumens vs the total proposed lumens, shielded and unshielded. (a) Show the lighting area (E3). (b) Option used. (c) Lamp source color temperature of all the exterior luminaires. (d) Shielding type. (Full Cut Off) or (Unshielded) (e) Provide a statement whether a special inspection is required or not. Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |