Permit Number: T19CM05188
Parcel: 12709011P

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM05188
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2019 DAVID RIVERA ZONING REVIEW Approved
10/03/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 1; Sheet G000; Code Information: The second line in this information still indicates the 2012 IBC. Please revise.
2. Previous Comment 8; Sheet A003; Section 24A: It appears the footing reinforcement is located in the top and bottom of the footing. Please indicate "#5 @ 12" o.c. top and bottom".
3. Previous Comment 22; General: The Special Inspection Certificate with Parts A and B completed was not provided. This form may be found on the City of Tucson website (tucsonaz.gov/PDSD).
4. General: The structural calculations must be included with the resubmission set.
5. General: It would be helpful to our review if drawings were presented in the same order as indicated on the Sheet Index.
6. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
10/09/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change As requested per the previous electrical plan review comment #1,"Please address the following electrical plan review comments. Also provide a written response.
1. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd. See section 104 for plan submittal requirements." No compliance on the second submittal. The 2012 Tucson/Pima County Outdoor Lighting Code is not to be confused with the 2018 IECC.
10/18/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/18/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/23/2019 JOHN VAN WINKLE ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/07/2019 KROBLES1 OUT TO CUSTOMER Completed
10/23/2019 SBORZAK1 OUT TO CUSTOMER Completed