Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM04691
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/12/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The lighting area is E3a.. The maximum color source temperature output allowed is 3500K. Please revise the lumen calcs. Ref; 2012 Tucson/Pima County Outdoor Lighting Code, sections 401.1, 402.1. |
| 08/12/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the remarks for RTU-1,2,3,4 in the ventilation calculations that refer to RTU-7. If RTU-8 is deleted, revise the rooftop unit schedule. [Initial comment: Revise the ventilation calculations for RTU-6 using the occupancy criteria in Table 403.3.1.1, IMC 2018 (retail shipping/receiving and retail storage) and an Ev of 0.8. Reference: Section 403.3.1.1, IMC 2018.] 2. Comment not addressed. [Initial comment: Demonstrate energy code compliance for the building envelope using calculations based on the current code. Reference: Sections C103.2, C303, and C401.2, International Energy Conservation Code 2018]. |
| 08/12/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/13/2019 | PMARTIN1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 08/13/2019 | PMARTIN1 | ENGINEERING | REVIEW | Needs Review | |
| 08/13/2019 | PMARTIN1 | WATER | REVIEW | Needs Review | |
| 08/13/2019 | PMARTIN1 | ZONING | REVIEW | Needs Review |