07/18/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet CS - Sheet Index - sheet H4.0 is noted but not attached to plan set , sheets E8.0 and sheet P4.0 are attached to plan set but not noted in Index . IBC 107.2.1.
2. Sheet S1.2 - Provide the description of the west masonry exterior wall and illustrate on plan . IBC 107.2.1.
3. Provide a completed Special Inspection Form for this project. IBC 107.2.1.

Respond to plan review comments in writing.
07/18/2019 ROBERT SHERRY WATER REVIEW Reqs Change 1. Show the location and sizes of the proposed water meter, backflow preventer, and the water service pipe on a site plan. Reference: Section 107.2.5, IBC 2018.
2. Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings, not double check valves. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
3. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water (i.e. not inside of the building). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
07/18/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2018.
2. Provide a site drawing showing the size, route, and slope of the building sewer and the location of its connection to the public sewer. Reference: Section 107.2.1, IBC 2018.
3. Provide underground facility tracer wires per ARS 40-360.22.
4. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2018.
5. Verify that the specified sensor faucet for the public lavatories has an automatic time-out so that it will dispense a maximum of 0.25 gallons per metering cycle. The faucet cycle shall last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
6. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
7. The "vacuum breaker" shown in detail 6/P3.0 is supposed to be a vacuum relief valve. Reference: Section 504.1, IPC 2018.
8. Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
9. A common vent is limited to serving two traps or trapped fixtures. Reference: Section 911.1, IPC 2018.
07/19/2019 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change Sheet E8.0 - All outdoor illuminating devices shall be installed in conformance with The City of Tucson / Pima County Outdoor Lighting Code . Provide conformance with this code , and illustrate on plan . IBC 107.2.1.
07/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the ventilation calculations for RTU-6 using the occupancy criteria in Table 403.3.1.1, IMC 2018 (retail shipping/receiving and retail storage) and an Ev of 0.8. Reference: Section 403.3.1.1, IMC 2018.
2. Keynote 17 on sheet H1.0 calls for the installation of a CO2 monitor in the sales area. Provide the sequence of operation associated with the CO2 monitor. Reference: Section 107.2.1, IBC 2018.
3. Demonstrate energy code compliance for the building envelope using calculations based on the current code. Reference: Sections C103.2, C303, and C401.2, International Energy Conservation Code 2018.
4. Show how the control for the vestibule complies with the requirements of Section C403.4.1.4, IECC 2018.
5. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Sections C403.4.1.3, C403.4.2.1, C403.4.2.2, and C403.4.2.3 IECC 2018.
07/26/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM04691 - New Building (Retail - General Merchandise)
Building Plan Review (1st Review) Michaels / Related to DP19-0166
3742 W. River Road / C-1 -C-2 Zoning

TRANSMITTAL DATE: July 26, 2019

DUE DATE: July 30, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans for compliance with the approved development package. While the building plans are consistent with the approved DP as it relates to the zoning review purview of the Building footprint, Height, square footage, site conditions etc., zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP.

3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
07/29/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change 1) Engineering will finally review and approve the building plans once all outstanding commercial reviews are complete

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2019 AMARTIN1 OUT TO CUSTOMER Completed