Permit Number: T19CM04089
Parcel: 112052790

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM04089
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Revise the NEC references to 2017.
2. Revise the new range receptacle to 4 wire and provide the correct symbol on the electrical floor plans that also correlates with the symbol plan. NEC 250.140.
3. Ref; Plan Sheet EP111, EP112The keynote #2 calls out #8 conductors for the range circuit and the panel schedule calls out #4. Please clarify.
4. Provide the values for total KVA, Total Amps, Total Load KVA on the panel schedule.
5. Ref; Plan Sheet E-601.
(a) Provide a complete line diagram with all the data and information required per the City of Tucson Commercial Plan Submittal Requirements (Electrical) www.tucsonaz.gov/pdsd
(b) Clarify Keynotes # 4 calls out conduit for 400amps for the secondaries to SES # 1 and #3. Shouldn't this be Keynote #3? Please clarify.
(c) Grounding electrode system shall be common with all services installed on the same building or structure. NEC 250.58.
6. Ref; Plan Sheet ES111.
Provide more detail for the 3-#2 feeders on the roof run from the wireway to the 100 amp panel, FC unit, condenser. Is this typical for each unit? Please clarify.
7. Be Advised that this review does not include the power and wiring methods for the AC units. See Plan Sheet E-001 'SCOPE FO WORK' Note D.
Ref; 2018 IBC sec 107.2.1, 2017 NEC art 210, 230, 240, 300, 310.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/12/2019 AMARTIN1 OUT TO CUSTOMER Completed