Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM03868
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/31/2019 | ELISA HAMBLIN | ZONING | REVIEW | Approved | |
05/31/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating/cooling load calculations for the two new A/C units. Note that the design temperature for Tucson is 104 degrees Fahrenheit. 2. Cooking appliances that are not required to have a hood are required to have general exhaust at 0.70 CFM per square foot. The basis for the exhaust is 100-square feet per appliance. Reference: Section 507.3, IMC 2018. |
05/31/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Correlate new panel numbers with the electrical floor plans. 2. Please provide full compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting.. Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |
05/31/2019 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
05/31/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/31/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/31/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The developed pipe length from the water heater to the furthest sink appears to be over 50-feet. Provide a recirculation system or heat-trace system. reference: Section 607.2, IPC 2018. 2. The specified water heater has a side inlet for the cold water. Provide a vacuum relief valve. reference: Section 504.2, IPC 2018. 3. Provide a structural design and calulations for the water heater support platform and show how the platform is attached to the wall. |
05/31/2019 | JPEELDA1 | FIRE | REVIEW | Approved | |
05/31/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/31/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
05/31/2019 | QJONES1 | REJECT SHELF | Completed |
05/31/2019 | QJONES1 | APPROVAL SHELF | Completed |