05/21/2020 ALEXANDRA HINES ZONING REVIEW Reqs Change 1) The addition of the concrete slab, canopy and relocation of existing parking spaces requires the submittal of a seperate Site Plan Development Package. Submittal requirments can be found in the City of Tucson Administrative Manual section 2-06. Once the development package has been submitted and approved the building plans will be reviewed for consistency.
05/21/2020 MARTIN BROWN FIRE REVIEW Approved
05/21/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T19CM03731

1) The addition of the concrete slab, canopy and relocation of existing parking spaces requires the submittal of a seperate Site Plan Development Package. Submittal requirments can be found in the City of Tucson Administrative Manual section 2-06. Once the development package has been submitted and approved the building plans will be reviewed for consistency

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
05/21/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S2.0 (Roof Framing Plan); Structural Calculations (Page 5): The calculations indicate the west canopy beam as a 3.125 x 13.5, while the Roof Framing Plan indicates a 3 1/8" x 12" GLB. Please coordinate.
2. General: Please add structural general notes as required.
3. General: Please provide a Special Inspection Certificate with Parts A and B completed.
4. General: Please provide written responses to all review comments.