Permit Number: T19CM03731
Parcel: 107031520

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM03731
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The lavatory located in the public restroom off the exercise room needs to have the hot water source within the maximum distance shown in Table C404.5.1, IECC 2018. [Second comment: The distance from the hot water source (i.e. the hot water recirculation system) to the lavatories in the public restrooms exceeds the maximum distance shown in Table C404.5.1, IECC 2018.] [Initial comment: Verify that the distance to the hot water termination from the hot water source complies with the requirements of Section C404.5, IECC 2018.]
07/26/2019 ALEXANDRA HINES ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2019 AVAUGHN1 APPROVAL SHELF Completed
07/30/2019 AVAUGHN1 OUT TO CUSTOMER Completed