Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2019 ALEXANDRA HINES ZONING REVIEW Reqs Change RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Please resubmit updated drawings along with a detailed comment response letter, which states how all zoning review comments were addressed.

Updates were made to building plans that affect zoning requirements. The comments are as follows:

1. Provide the correct land use per the previous zoning review: Civic Land Use Group, Membership Organization Land Use per use specific standard UDC 4.9.13.Q.
2. Provide the correct required number of parking per Membership Organization Land Use: 1 space per 100 SF GFA in public assembly areas. From sheet A1.0, use the A-3 SF minus the Warming Kitchen SF for the public assembly area. It seems like the calculation may comply with the 32 stalls provided.
3. Provide detail and note of wall mounted accessible parking sign. Sign shall be mounted at 5-foot height. Add a separate "van accessible" sign below the main sign as required. It does not seem like a ground mounted sign will comply with circulation path.
4. Provide the access aisle and ramp slopes on sheet A1-0 to showcase compliance. Access aisle shall be maximum 2% slope in all directions. Ramp shall be maximum 1:12 slope.
5. Provide a van accessible parking space at 16 feet wide for whole length of space. The other accessible parking space shall be 13 feet wide for whole length of space. Curb ramps and landings shall be 3 feet minimum in width, exclusive of flared sides. It seems like modifying the ramp or other parking space widths will bring van accessible parking space to compliance.

Zoning will review the building plans on the next submittal to assure that any updates made to the building plans does not affect zoning requirements.

If you have any questions about this transmittal, contact Alexandra Hines at 520-837-6975 or alexandra.hines@tucsonaz.gov.
07/19/2019 AHINES2 ELECTRICAL-COMMERCIAL REVIEW Approved Per signature on review card.
07/19/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The distance from the hot water source (i.e. the hot water recirculation system) to the lavatories in the public restrooms exceeds the maximum distance shown in Table C404.5.1, IECC 2018. [Initial comment: Verify that the distance to the hot water termination from the hot water source complies with the requirements of Section C404.5, IECC 2018.]
07/19/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
07/19/2019 JPEELDA1 FIRE REVIEW Approved
07/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed