Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM03731
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/05/2019 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Indicate door 101C as 90min fire rated. Clearly identify location of all doors having panic hardware. |
| 06/07/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0 - Code Plan - illustrate the means of egress . IBC 107.2.1. 2. Sheet A1.0 - Code Plan - occupant load calculations for B occupancy are incorrect . IBC 107.2.1. 3. Sheet A1.0 - Code Plan - conference room is designated a A-3 occupancy , conference room is a B occupancy . IBC 304. 4. Sheet A1.0 - Code Plan - Chapter 29 - Plumbing Systems - provide Minimum Number of Required Plumbing Fixtures per IBC Table 2902.1 . IBC 107.2.1. 5. Sheet A1.0 - provide means of egress sizing calculations . IBC 1005. 6. Sheet A1.0 - Training Room is designated an A-3 occupancy , training room is a B occupancy . IBC 304. Respond to plan review comments in writting . Cloud all revisions . |
| 06/12/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/13/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. All plumbing fixtures being provided by others (e.g. dishwasher) shall be third-party listed. Reference: Sections 303.4 and 402, IPC 2018. 2. If the discharge temperature of the dishwasher will be greater than 140 degrees Fahrenheit, show that the temperature rating of the drainage pipe material is suitable for the highest temperature of the wastewater. Reference: Section 702.5, IPC 2018. 3. Verify that the distance to the hot water termination from the hot water source complies with the requirements of Section C404.5, IECC 2018. |
| 06/13/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the cooling/heating loads for the building to coordinate with the proposed mechanical design. Reference: Section 107.2.1, IBC 2018. |
| 06/27/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Illustrate Exit Lighting on sheet A6 - Reflected Ceiling Plan and Details , and sheet E1.0 - Lighting Plan . IBC 107.2.1. |
| 07/05/2019 | DAVID RIVERA | ZONING | REVIEW | Approved |