Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM03731
Parcel: 107031520

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM03731
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2019 JPEELDA1 FIRE REVIEW Reqs Change Indicate door 101C as 90min fire rated. Clearly identify location of all doors having panic hardware.
06/07/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0 - Code Plan - illustrate the means of egress . IBC 107.2.1.
2. Sheet A1.0 - Code Plan - occupant load calculations for B occupancy are incorrect . IBC 107.2.1.
3. Sheet A1.0 - Code Plan - conference room is designated a A-3 occupancy , conference room is a B occupancy . IBC 304.
4. Sheet A1.0 - Code Plan - Chapter 29 - Plumbing Systems - provide Minimum Number of Required Plumbing Fixtures per IBC Table 2902.1 . IBC 107.2.1.
5. Sheet A1.0 - provide means of egress sizing calculations . IBC 1005.
6. Sheet A1.0 - Training Room is designated an A-3 occupancy , training room is a B occupancy . IBC 304.

Respond to plan review comments in writting .
Cloud all revisions .
06/12/2019 ROBERT SHERRY WATER REVIEW Completed
06/13/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. All plumbing fixtures being provided by others (e.g. dishwasher) shall be third-party listed. Reference: Sections 303.4 and 402, IPC 2018.
2. If the discharge temperature of the dishwasher will be greater than 140 degrees Fahrenheit, show that the temperature rating of the drainage pipe material is suitable for the highest temperature of the wastewater. Reference: Section 702.5, IPC 2018.
3. Verify that the distance to the hot water termination from the hot water source complies with the requirements of Section C404.5, IECC 2018.
06/13/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the cooling/heating loads for the building to coordinate with the proposed mechanical design. Reference: Section 107.2.1, IBC 2018.
06/27/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Illustrate Exit Lighting on sheet A6 - Reflected Ceiling Plan and Details , and sheet E1.0 - Lighting Plan . IBC 107.2.1.
07/05/2019 DAVID RIVERA ZONING REVIEW Approved