Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM03517
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/23/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G1.0 - CH 29 Plumbing Systems - Per ANSI A117.1 Exception 602.4 , the exception noted is not correct , use correct code reference . IBC 107.2.1. 2. Sheet G1.0 - CH 10 Means of Egress - Number of Exits Required ( Table 1006.3.3(2) for B Occupancy ) is not correct , use correct code reference . IBC 107.2.1. |
| 05/29/2019 | MROSS2 | FIRE | REVIEW | Approved | |
| 06/04/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Tucson water shows a water pressure range of 41 to 48 PSI at the project address. The pressure loss calculations for the shell building (KC Mechanical, 8/10/18) are based on 48 PSI and call for a booster pump. Section 604.1, IPC 2018 allows the use of accepted engineering practice to design water distribution systems but the design must be consistent with the selected engineering practice. Revise the pressure calculations using the minimum available water pressure. Reference: Section A1.1, UPC 2012. 2. For public toilet facilities, the required lavatory shall be located in the same room as the water closet. If the unisex restroom 125 is for lab testing purposes, the water closet and lavatory cannot be counted with the required plumbing fixtures in the building code analysis. Reference: Section 405.3.2, IPC 2018. 3. Verify that the distances to the hot water termination points from the hot water source comply with the requirements of Section C404.5, IECC 2018. |
| 06/05/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/05/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The lab has 265 CFM of exhaust. What is being exhausted? Reference: Section 107.2.1, IBC 2018. 2. The Med Room does not appear to be a storage room due to the sink located in the room. What activities are happening in that room? Reference: Section 403.3.1.1, IMC 2018. |
| 06/11/2019 | PMARTIN1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |