Permit Number: T19CM03325
Parcel: 141186260

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL TI

Permit Number - T19CM03325
Review Name: 3RD PARTY REVIEW - COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2019 MARTIN BROWN FIRE REVIEW Reqs Change Please clearly define where panic hardware will be installed. Note for patio gate (sheet A-601) is confusing. Is this a gate or a door? Must comply with 2018 IBC for exit doors.
05/24/2019 ROBERT SHERRY WATER REVIEW Completed
06/10/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T19CM03325

1) Update sheet A-002 to reflect the approved site plan shown in the approved version of DP19-0008
2) Engineering can approve the plans once the above comment and all outstanding department reviews have been completed and approved

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
06/10/2019 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: MOD - Houghton Town Center
T19CM03325
Building Plan (1st Review)

TRANSMITTAL DATE: June 10, 2019

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans have been reviewed for compliance with development package S11-0440 and although it appears that the building plans meet the requirements of S11-0440 Zoning cannot approve the building plans until approved by all other PDSD and 3rd Party review agencies.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
06/24/2019 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/24/2019 PMARTIN1 OUT TO CUSTOMER Completed