Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM03306
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/10/2019 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Based on occupant load, both doors serving Dining Hall (room B-001) must swing in the direction of travel. Sheet ES1.1 indicates voice evac for only E occupancy spaces. Per 2018 IBC, table 707.3 10, two hour separation would be required to create separate fire areas (2018 IFC, section 901.4.3. This would apply to the first and second floor as well. |
07/11/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/17/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Using alternative occupancy rates for the ventilation calculations requires the submission of an appeal to the building official. Reference: Section 104.11, IBC 2018. [Initial comment: The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3.1.1, IMC 2018 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3.1.1, IMC 2018.] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/08/2019 | AVAUGHN1 | REJECT SHELF | Completed |