Permit Number: T19CM02818
Parcel: 117120310

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM02818
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
As requested per previous plan review comments #1. Coordinate with Mech. And Plumbing and provide power for the insta-hot water heater and the exhaust fan required in the lab. The 20 amp overcurrent device called out for the insta-hot water heater is undersized for a 10KW unit. Also provide for a disconnect switch at its location Per NEC.
2. Provide for tamper resistant receptacles as required per 2017 NEC art 406.12(5).
Ref; 2017 NEC, 2018 IBC sec 107.2.1.