Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM02818
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/13/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. As requested per previous plan review comments #1. Coordinate with Mech. And Plumbing and provide power for the insta-hot water heater and the exhaust fan required in the lab. The 20 amp overcurrent device called out for the insta-hot water heater is undersized for a 10KW unit. Also provide for a disconnect switch at its location Per NEC. 2. Provide for tamper resistant receptacles as required per 2017 NEC art 406.12(5). Ref; 2017 NEC, 2018 IBC sec 107.2.1. |