Permit Number: T19CM02818
Parcel: 117120310

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM02818
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2019 ALEXANDRA HINES ZONING REVIEW Approved
04/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide exhaust for lab per the ventilation calculations.
04/19/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Coordinate with Mech. And Plumbing and provide power for the insta-hot water heater and the exhaust fan required in the lab.
2. Provide for tamper resistant receptacles as required per 2017 NEC art 406.12(5).
Ref; 2017 NEC, 2018 IBC sec 107.2.1.
04/19/2019 AHINES2 ENGINEERING REVIEW Passed
04/19/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
04/19/2019 ROBERT SHERRY WATER REVIEW Completed
04/19/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/19/2019 MARTIN BROWN FIRE REVIEW Approved
04/19/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed