Permit Number: T19CM02703
Parcel: 14043013B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM02703
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 1; Sheet S1; Structural Steel Notes: No response was located from the parent building Engineer of Record for the foundation design.
2. Previous Comment 2; Sheet S1: An updated code reference to the 2018 IBC was not located on this sheet. Please provide.
3. Previous Comment 7; General: The Special Inspection Certificates provided need to have Parts A and B completed. Please provide.
05/23/2019 PMARTIN1 FIRE REVIEW Needs Review