Permit Number: T19CM02703
Parcel: 14043013B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM02703
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1; Structural Steel Notes: Note 12 indicates a foundation design and analysis for this structure shall be provided by the parent building engineer. Please provide that design.
2. Sheet S1: Please indicate on this sheet the 2018 IBC was used for the structural design requirements.
3. Sheet S2.1; Elevation 1: Was a structural calculation provided for the W16x26 beams? Please verify.
4. Sheet S2.2 (Detail 10); Structural Calculations (Pages 18 and 19): The calculations indicate the epoxy anchors require 10" of embedment, while the detail indicates 9" minimum embedment. Please coordinate.
5. Sheet S2.2; Detail 10 Expansion Anchor: Was a structural calculation provided for the expansion anchors? Please verify.
6. Structural Calculations; Page 1: Please revise the code reference to the 2018 IBC.
7. General: Please provide a Special Inspection Certificate with Parts A and B completed.
8. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
04/24/2019 MROSS2 FIRE REVIEW Reqs Change Please provide some kind of code anaylsis. specifically wether or not the chamber will be alarmed and sprinklered. Add note to plan indicating sprinklers and alarms will be deferred submittals.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/01/2019 QJONES1 APPROVAL SHELF Completed
05/01/2019 QJONES1 OUT TO CUSTOMER Completed
05/01/2019 QJONES1 REJECT SHELF Completed