Permit Number: T19CM02427
Parcel: 13012185A

Address:
3825 E 32ND ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T19CM02427
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2019 NICHOLAS ROSS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Nick Ross
Lead Planner

PROJECT:
T19CM02427
3825 E 32 Street
New Porch, Carport and Storage

TRANSMITTAL: Date
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The applicant is proposing a 1' setback on east side of the property. The structure is 7'10" and requires a 6' setback. DDO is required.
06/03/2019 NROSS1 ENGINEERING REVIEW Passed
06/03/2019 NROSS1 NPPO REVIEW Passed
07/18/2019 ARUIZ1 BUILDING-RESIDENTIAL REVIEW Needs Review