Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2019 MROSS2 FIRE REVIEW Approved
05/01/2019 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
05/01/2019 KROBLES1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 33; Special Inspection Certificate: The Special Inspection Certificate must indicate, for each inspection category, the name of the ICC certified special inspector that will be performing each inspection. Please provide on the certificate.
2. Sheet S1.101B; Foundation Plan: At Brace Frame 2 (Grid C), a Keynote 7 is referenced at both columns, indicating a concrete pedestal poured monolithically with the elevator pit walls. Please verify. Sheet S5.001 does not indicate a pedestal.
3. Sheet S5.001 (Brace Frames 1, 2, and 3); Structural Calculations (Sheet 320): The 3/29/2019 response letter from PK Associates indicates the chevron brace frames were changed to K braced frames per the calculation package. Sheet S5.001 indicates the K braced frames 1, 2, and 3, but the calculation package Sheet 320 indicates the chevron brace frames. Please coordinate and revise the calculations as required. Are the footing sizes affected by this change? Please verify.
4. Sheet S5.001; Brace Frame 2: Detail C is indicated at the column base on Grid Line BB. Please verify.
5. General: Please provide written responses to all review comments.
05/13/2019 JOHN VAN WINKLE ENGINEERING REVIEW Approved
05/13/2019 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/14/2019 PMARTIN1 OUT TO CUSTOMER Completed