Permit Number: T19CM02154
Parcel: 128030100

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM02154
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
08/16/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide calculations demonstrating compliance with the 2018 IECC (e.g. COMcheck for the envelope).
2. Coordinate the mechanical heating/cooling load calculations, the mechanical COMcheck, and the mechanical design.
3. If reduced interior lighting power is being used to satisfy the requirements of Section C406, IECC, the tenant improvements will have to provide reduced lighting power.
08/16/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide roof drain calculations.
2. Provide secondary roof drainage.
08/16/2019 MARTIN BROWN FIRE REVIEW Approved
08/16/2019 ROBERT SHERRY WATER REVIEW Reqs Change Provide a water meter located on the correct land parcel.
08/23/2019 AMARTIN1 BUILDING-COMMERCIAL REVIEW Needs Review
08/23/2019 AMARTIN1 ENGINEERING REVIEW Needs Review
08/23/2019 AMARTIN1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/23/2019 AMARTIN1 ZONING REVIEW Needs Review