Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM02154
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/16/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 08/16/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide calculations demonstrating compliance with the 2018 IECC (e.g. COMcheck for the envelope). 2. Coordinate the mechanical heating/cooling load calculations, the mechanical COMcheck, and the mechanical design. 3. If reduced interior lighting power is being used to satisfy the requirements of Section C406, IECC, the tenant improvements will have to provide reduced lighting power. |
| 08/16/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide roof drain calculations. 2. Provide secondary roof drainage. |
| 08/16/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/16/2019 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide a water meter located on the correct land parcel. |
| 08/23/2019 | AMARTIN1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 08/23/2019 | AMARTIN1 | ENGINEERING | REVIEW | Needs Review | |
| 08/23/2019 | AMARTIN1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/23/2019 | AMARTIN1 | ZONING | REVIEW | Needs Review |