Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM02018
Parcel: 10819009B

Address:
4798 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM02018
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change Please respond to all plan review comments in writting .
The Structural Calculations - Drilled Pier Reinforcing Design - states : USE 2#5 Each Side Of Column . Plan sheet S2 - A1 - Drilled Pier Footing - Does not specify - USE 2#5 Each Side Of Column . Please clarify on plan . IBC 107.2.1
04/16/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the proposed exterior lighting.
2. The inverter spec date information text size needs to be enlarged to a minimum of 3/32". Need to verify disconnecting requirements at the inverter are met per 690.13, 705.70.
3. Verify ground fault detection and disconnection of the dc source circuits as required per 690.41B.
4. Provide the distance above grade for the inverters on the inverter mounting detail, plan sheet PV-5.
5. Provide canopy, modular, and rack grounding details. Verify the requirements of 690.43B are met.
Ref; 2017 NEC, Tucson/Pima County Outdoor Lighting Code.
04/19/2019 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/29/2019 PMARTIN1 OUT TO CUSTOMER Completed