Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM02018
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/22/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please respond to all plan review comments in writting . The Structural Calculations - Drilled Pier Reinforcing Design - states : USE 2#5 Each Side Of Column . Plan sheet S2 - A1 - Drilled Pier Footing - Does not specify - USE 2#5 Each Side Of Column . Please clarify on plan . IBC 107.2.1 |
04/16/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the proposed exterior lighting. 2. The inverter spec date information text size needs to be enlarged to a minimum of 3/32". Need to verify disconnecting requirements at the inverter are met per 690.13, 705.70. 3. Verify ground fault detection and disconnection of the dc source circuits as required per 690.41B. 4. Provide the distance above grade for the inverters on the inverter mounting detail, plan sheet PV-5. 5. Provide canopy, modular, and rack grounding details. Verify the requirements of 690.43B are met. Ref; 2017 NEC, Tucson/Pima County Outdoor Lighting Code. |
04/19/2019 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/29/2019 | PMARTIN1 | OUT TO CUSTOMER | Completed |