Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM01996
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/15/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/15/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G121; Life Safety Plan: Per the IBC Section 1017.3, measurement of the exit access travel distance shall be along the natural and unobstructed path of horizontal and vertical egress travel. Please revise the diagonal paths shown and the travel distances, and verify those distances meet the code requirements. 2. Sheet G121; Life Safety Plan: Two notes indicate "Existing 2 hour horizontal separation barrier". Please revise the notes to indicate existing 2 hour fire resistant rated barrier separation partition. 3. Sheet G122; Life Safety Plan: Per the IBC Section 1017.3, measurement of the exit access travel distance shall be along the natural and unobstructed path of horizontal and vertical egress travel. Please revise the diagonal paths shown and the travel distances, and verify those distances meet the code requirements. 4. Sheet G122; Life Safety Plan: Per the IBC Section 1020.4, dead end corridors shall not exceed 20 feet in length unless one of the Exceptions applies. Please verify the exit path from the President Office to the Open Work area meets that requirement. 5. Sheet S122; Detail 8 (Elevation A): The 1/4 x 4 x 0'-6" plate note has an arrow that does not point to the proper plate. Please revise. 6. Sheet S302; Detail 2: The tube above the hanger support indicates a HSS4 x 24 x 1/4. Please revise. 7. General: Please provide written responses to all review comments. |
04/18/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
04/18/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. |
04/18/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
04/22/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide clarification as to the scope of work for the new power and lighting installations. Some of the areas clouded in have no delta symbol or reference notations on the electrical and lighting floorplans, or there is a delta symbol with no reference notes. For example; is all the lighting new shown on the first floor lighting plan sheet 'ED321A', 'ED322A'? Provide information for the clouded in outlets. Etc. 2. Assign a branch circuit and panel designation for all outlets. Ref; 2017 NEC 408.4, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements. |
04/23/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/29/2019 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
05/01/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/08/2019 | TWEIDEM1 | APPROVAL SHELF | Completed |
05/08/2019 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
05/08/2019 | TWEIDEM1 | REJECT SHELF | Completed |