Permit Number: T19CM01996
Parcel: 12310001H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM01996
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/15/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G121; Life Safety Plan: Per the IBC Section 1017.3, measurement of the exit access travel distance shall be along the natural and unobstructed path of horizontal and vertical egress travel. Please revise the diagonal paths shown and the travel distances, and verify those distances meet the code requirements.
2. Sheet G121; Life Safety Plan: Two notes indicate "Existing 2 hour horizontal separation barrier". Please revise the notes to indicate existing 2 hour fire resistant rated barrier separation partition.
3. Sheet G122; Life Safety Plan: Per the IBC Section 1017.3, measurement of the exit access travel distance shall be along the natural and unobstructed path of horizontal and vertical egress travel. Please revise the diagonal paths shown and the travel distances, and verify those distances meet the code requirements.
4. Sheet G122; Life Safety Plan: Per the IBC Section 1020.4, dead end corridors shall not exceed 20 feet in length unless one of the Exceptions applies. Please verify the exit path from the President Office to the Open Work area meets that requirement.
5. Sheet S122; Detail 8 (Elevation A): The 1/4 x 4 x 0'-6" plate note has an arrow that does not point to the proper plate. Please revise.
6. Sheet S302; Detail 2: The tube above the hanger support indicates a HSS4 x 24 x 1/4. Please revise.
7. General: Please provide written responses to all review comments.
04/18/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/18/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
04/18/2019 ROBERT SHERRY WATER REVIEW Completed
04/22/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide clarification as to the scope of work for the new power and lighting installations. Some of the areas clouded in have no delta symbol or reference notations on the electrical and lighting floorplans, or there is a delta symbol with no reference notes. For example; is all the lighting new shown on the first floor lighting plan sheet 'ED321A', 'ED322A'? Provide information for the clouded in outlets. Etc.
2. Assign a branch circuit and panel designation for all outlets.
Ref; 2017 NEC 408.4, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements.
04/23/2019 MARTIN BROWN FIRE REVIEW Approved
04/29/2019 STEVE SHIELDS ZONING REVIEW Approved
05/01/2019 LOREN MAKUS ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2019 TWEIDEM1 APPROVAL SHELF Completed
05/08/2019 TWEIDEM1 OUT TO CUSTOMER Completed
05/08/2019 TWEIDEM1 REJECT SHELF Completed