Review Details: POST 3RD PARTY REVIEW

Permit Number - T19CM01829
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2019 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T19CM01829
Shell Building Plan (1st Review)
6442 E SPEEDWAY BL - O-1 Zoning

TRANSMITTAL DATE: October 18, 2019


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: COMMENT: Zoning has reviewed the plan and cannot approve at this time. Please address the following comments.


02. COMMENT: The building height is measured from design grade not finished floor area. Per UDC section 6.4.4.A. The max height in an O-1 zone is 16'.





If you have any questions about this transmittal, Contact Paul Camarena any time during the week at (520) 837-4082 or by email Paul.Camarena@Tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
10/18/2019 ROBERT SHERRY WATER REVIEW Completed
10/21/2019 MARTIN BROWN FIRE REVIEW Reqs Change Please review section 5306 of the 2018 International Fire Code. Clearly indicate on plans how all components of the code are being satisfied, including fire ratings, ventilation, etc. for the med gas storage room.
Lobby requires a second exit door that swings in the direction of egress travel. Choose one of the other doors (101A or 101B) to swing in the direction of egress travel. This will result in you having to modify exiting plan and exit sign placement.
Please delineate changes in a response letter.
10/22/2019 QJONES1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/31/2019 QJONES1 OUT TO CUSTOMER Completed