Permit Number: T19CM01757
Parcel: 125081150

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM01757
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. As requested at the previous plan review comment #2 for power and lighting outlets for the above ceiling FC units. The NEC requires a receptacle and switched lighting outlet. Also designate a branch circuit and panel. NEC 210.63, 210.70A(3).
2. As requested at the previous plan review comment #3. The City of Tucson does not recognize as builds. As requested, please provide designated branch circuits and panels, include switching for the lighting as required per the 2018 IECC.
Ref: 2018 IBC sec 107.2.1, 2018 IECC, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
05/17/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/17/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The total and sensible cooling capacities for rooftop units RTU-1, 2, 3, 5, 6, 8, and 10 appear to be greater than required based on the cooling load calculations. Verify the unit selections. Reference: Section C403.1.1, IECC 2018. [Second comment: The calculations only show the sensible cooling loads and the schedule only shows the total cooling capacity of the units. Please add a bit more information.] [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified rooftop units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.]

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2019 QJONES1 APPROVAL SHELF Completed
06/28/2019 QJONES1 OUT TO CUSTOMER Completed
06/28/2019 QJONES1 REJECT SHELF Completed