Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T19CM01757
Parcel: 125081150

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM01757
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Provide an auxiliary or secondary condensate drain system for the fan coils. Reference: Section 307.2.3, IMC 2018]
2. Keynote 3 on sheet M1.1 calls for connecting a new 8" duct to an existing exhaust duct for the restrooms. I can't find keynote 3 (or keynote 2 for that matter) on sheet M1.1. If you are modifying the ductwork, will the fan have to be rebalanced? [Initial comment: See Table 403.3.1.1 for the minimum exhaust flow rates needed for restrooms (i.e. the flow rate is determined by both the number of water closets and urinals in each room as well as continuous operation versus intermittent operation of the fan). Reference: Section 403.2.1 (4) and 403.2.2, IMC 2018.]
3. The calculations only show the sensible cooling loads and the schedule only shows the total cooling capacity of the units. Please add a bit more information. [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified rooftop units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
05/10/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Sheet A1.1 still shows the relocation of WH-1. [Initial comment: The replacement and relocation of the water heater appears to have resulted in domestic hot water supply piping with a developed length in excess of fifty-feet. Provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018.]
05/17/2019 PMARTIN1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. As requested at the previous plan review comment #2 for power and lighting outlets for the above ceiling FC units. The NEC requires a receptacle and switched lighting outlet. Also designate a branch circuit and panel. NEC 210.63, 210.70A(3).
2. As requested at the previous plan review comment #3. The City of Tucson does not recognize as builds. As requested, please provide designated branch circuits and panels, include switching for the lighting as required per the 2018 IECC.
Ref: 2018 IBC sec 107.2.1, 2018 IECC, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.