Permit Number: T19CM01638
Parcel: 141153530

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM01638
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet AD1.1; Demolition Floor Plan: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the grid designations.
2. Sheet AD1.1; Demolition Floor Plan: There are many keynotes listed that were not located on the plan. Please verify and add/remove keynotes as required, or indicate on the drawing all keynotes listed may not appear on this sheet (reference Sheets AD1.2 and AD1.3).
3. Sheets AD1.2 and AD1.3; Demolition Floor Plan: There are many keynotes listed that were not located on the plan. Please verify and add/remove keynotes as required, or indicate on the drawing all keynotes listed may not appear on this sheet (reference Sheets AD1.1, AD1.2, or AD1.3).
4. Sheet AD1.3; Demolition Floor Plan: Note 44 states "Hatch indicates area of existing concrete slab being removed-Refer to 2/A1.2". The hatch does not show up on this plan. Please revise.
5. Sheet A1.1; Floor Plan: Note 13 was not located on the plan. Please verify.
6. Sheet S1.0; Foundation Plan: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the dimensions.
7. Sheets S1.0 and S1.1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the dimensions.
8. Sheet S1.3; Detail 10: The title indicates an existing CMU wall. It is a new CMU wall. Please revise the title.
9. General: Please provide written responses to all review comments.
03/25/2019 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Approved
03/25/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/25/2019 RMCCOY1 WATER REVIEW Approved
04/03/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Sheet E7.1 - IECC Com Check Report - the interior lighting compliance report is missing , please submit the Lighting Compliance Report . IBC 107.2.1.
04/08/2019 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: 8080 S Houghton Rd
T19CM01638
Store Expansion (1st Review)

TRANSMITTAL DATE: April 8, 2019

1. As the proposed TI is an expansion of floor area a development package in substantial compliance with Administrative Manual 2-06 will need to be submitted and approved prior to approval of the TI plans.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

Final Status

Task End Date Reviewer's Name Type of Review Description
05/02/2019 QJONES1 APPROVAL SHELF Completed
05/02/2019 QJONES1 OUT TO CUSTOMER Completed
05/02/2019 QJONES1 REJECT SHELF Completed