Permit Number: T19CM00615
Parcel: 11522129A

Address:
1637 W EL RIO DR

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM00615
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/09/2019 ROBERT SHERRY WATER REVIEW Completed
04/09/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/09/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revised drawings were not submitted. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation of the new building. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.]
2. Revised drawings were not submitted. [Initial comment: Revise the location of the expansion tank in the water heater detail so that the check valve is not between the water heater and the expansion tank. Reference: Section 607.3, IPC 2018.
04/11/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/01/2019 QJONES1 APPROVAL SHELF Completed
05/01/2019 QJONES1 OUT TO CUSTOMER Completed
05/01/2019 QJONES1 REJECT SHELF Completed