Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T19CM00615
Parcel: 11522129A

Address:
1637 W EL RIO DR

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T19CM00615
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a site drawing showing the size, route, and slope of the building sewer and the location of its connection to the public sewer or a private sewer collection system. Reference: Section 107.2.1, IBC 2018.
2. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation of the new building. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
3. Revise the location of the expansion tank in the water heater detail so that the check valve is not between the water heater and the expansion tank. Reference: Section 607.3, IPC 2018.
02/13/2019 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly serving this building. Reference: Section 107.2.1, IBC 2018.
2. Provide the total water demand that the water meter will serve. Reference: Section 107.2.1, IBC 2018.
3. Per Tucson Water, the water pressure range for this address may be greater than 80 PSI. Provide a pressure reducing valve conforming to ASSE 1003 or CSA B356 with a strainer to reduce the water pressure to not more than 80 PSI. Reference: Section 604.8, IPC 2018.
02/14/2019 MARTIN BROWN FIRE REVIEW Approved
02/14/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The 2018 International Mechanical Code with Local Amendments is the relevant code for this project. Revise the IECC Notes and the ventilation calculations on sheet M3.2 accordingly.
2. Complete the COMcheck mechanical compliance certificate by listing the mechanical equipment. Verify that the efficiencies of the HVAC units comply with C406.2, IECC 2018. Reference: Section C103.2, IECC 2018.
3. Secure the refrigerant circuit access ports of the condensing units to prevent unauthorized access. Reference: Section 1101.10, IMC 2018.
02/15/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A0.1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the notes.
2. Sheets A0.2.1 through 0.2.4: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the accessibility notes.
3. Sheets A0.2.1 through A0.2.8: These sheets all indicate "For Reference Only". Many of these details are required. Please indicate the required details on a sheet not listed as "For Reference Only".
4. Sheet A0.7.1; Exiting Plan: The purpose of this plan is to show the exit access travel distance (as defined in the IBC Section 202), and to verify that distance (as measured per Section 1017.3) does not exceed the distance indicated in Table 1017.2. Please provide this information on the plan on Sheet A0.7.1.
5. Sheet A0.7.1; Exiting Plan: An exit sign is not required (as shown) for the door exiting from the mechanical room. Please verify.
6. Sheet A2.1.1; Symbols: The square box indicates assembly type indicated per A9.2 and A9.3. These sheets are not in this drawing set. Please verify.
7. Sheet A5.1.1; Reflected Ceiling Plan: Please indicate the exit signs on this plan.
8. Sheet A6.2.1; Keynote 6.48: This note references 8/A0.2.1 for a drinking fountain detail. Please add dimensions for the drinking fountain per the ICC/ANSI Figure 602.5.
9. General: No structural calculations were submitted with this project. Please provide.
10. General; Special Inspection Certificate: The designated special inspector (Pat Sullivan) is not included in the list of ICC certified special inspectors used by the City of Tucson. Please revise. An option is to list the name of Mr. Allen R. Miller, P.E., on all of the special inspections.
11. General: Please provide written responses to all review comments
02/15/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
02/25/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E1.1. The notes in the blocked boxes referring to separate permits is not clear. Explain or clarify what separate permits are referenced? Do the outdoor Lumen Calcs reflect total exterior luminaires on the parcel?
2. Provide for Tamper Resistant receptacles where applicable as required per NEC 406.12
3. Is FC1 and CU2 both on circuit 29-31, panel CA ? Please correlate equipment with the panel schedule.
Ref; 2018 IBC sec 107.2.1, 2017 NEC
02/26/2019 NICHOLAS ROSS ZONING REVIEW Approved
02/26/2019 NROSS1 ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/18/2019 QJONES1 APPROVAL SHELF Completed
03/18/2019 QJONES1 OUT TO CUSTOMER Completed
03/18/2019 QJONES1 REJECT SHELF Completed