Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM00120
Parcel: 11620134B

Address:
875 W CUSHING ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM00120
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change Please provide written responses to all plan review comments:
1. Provide GENERAL STRUCTURAL NOTES for this project that include: GENERAL REQUIREMENTS, SPECIAL INSPECTIONS, PRIMARY CODES AND SPECIFICATIONS for all applicable building materials and systems, SUBMITTALS, and STRUCTURAL DRAWING INDEX. IBC 1603
2. Provide an overall site plan that shows the location and types of all parking structures; include electrical circuit and lighting plans if they will be incorporated into the structures. IBC 107.2.1.
3. The edition of the building code in effect at the time of the plans submittal is the 2018 INTERNATIONAL BUILDIN CODE. Revise the structural calculations and re-evaluate the structural design based on the 2018 IBC

Final Status

Task End Date Reviewer's Name Type of Review Description
02/15/2019 QJONES1 APPROVAL SHELF Completed
02/15/2019 QJONES1 OUT TO CUSTOMER Completed
02/15/2019 QJONES1 REJECT SHELF Completed