Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T19CM00016
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/15/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/22/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet PV2.0; Site Plan: Please indicate the separation distance between all of the canopies on this sheet. 2. Sheets S2 and S3; Plan View: Canopy 5 is not referenced on any of the plan views. Please revise. 3. Sheet S5; Detail 101: Note 3 indicates 12 gauge purlins at 101A. Is that purlin size indicated in the drawings or calculations presented here? Remove from this sheet as required. 4. General: It would be helpful in the future if the steel frame model indicated in the calculations (pages 25 and 50 in this set) references the canopy number as shown in the drawings. 5. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 01/30/2019 | DAVID RIVERA | ZONING | REVIEW | Passed | |
| 01/31/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | T19CM00016 1) Show location of trash enclosure on plans and show required service vehicle maneuvering and clear area per City of Tucson Technical Standards Manual section 8 John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
| 01/31/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Ref; Plan Sheet PV3.0 1. Verify that the bus is marked 'TAP 'by the manufacturer at the proposed PV tap interconnection. Otherwise a field evaluation will be required for re-listing the service equipment. Ref; 2011 NEC 110.3, UL GUIDE FOR ELECTRICAL EQUIPMENT section 'WEVZ'. |