Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2019 MARTIN BROWN FIRE REVIEW Approved
01/14/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S2 (Plan View); Structural Calculations (Page 69): The calculations for this canopy indicate a W14x38 column, while the plan indicates a W14x34 column. Please verify.
01/28/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The supply side PV interconnection will require a field evaluation. Per UL, the existing bus holes must have the word "TAP" on the bus to be listed for such. Please Revise the plan to reflect this. Ref; www.ul.com, 2012 NEC art 110.3
2. Plan Sheet PV 4.0. Inverter "S1" does not correlate with the rest of the plans. Please clarify.
Ref; 2012 IBC sec 107.2.1, 2011 NEC
01/29/2019 DAVID RIVERA ZONING REVIEW Passed
01/30/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed