Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T18CM10028
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/14/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S2 (Plan View); Structural Calculations (Page 69): The calculations for this canopy indicate a W14x38 column, while the plan indicates a W14x34 column. Please verify. |
| 01/28/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The supply side PV interconnection will require a field evaluation. Per UL, the existing bus holes must have the word "TAP" on the bus to be listed for such. Please Revise the plan to reflect this. Ref; www.ul.com, 2012 NEC art 110.3 2. Plan Sheet PV 4.0. Inverter "S1" does not correlate with the rest of the plans. Please clarify. Ref; 2012 IBC sec 107.2.1, 2011 NEC |
| 01/29/2019 | DAVID RIVERA | ZONING | REVIEW | Passed | |
| 01/30/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed |