Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM09984
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/04/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/07/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Initial comment: Unless cups are available at an accessible location by the two drinking fountains, provide the number of drinking fountains that complies with the requirements of Section 1109.5.1, IBC 2012 and Section 410.2, IPC 2012.] 2. A shut off valve isolates the existing water heater from the expansion tank. [Initial comment: Show how accommodation for the thermal expansion of the hot water system is being provided for the existing water heater. Reference: Section 607.3, IPC 2012.] |
| 03/07/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide heating and cooling load calculations for fan coil FC-5. [Initial comment: Provide heating and cooling load calculations to verify that the proposed HVAC units together with the existing HVAC units are just sufficient to condition the building. Use the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/18/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 03/18/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 03/18/2019 | QJONES1 | REJECT SHELF | Completed |