Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM09984
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/09/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A0.1; Wall Types: Please provide the gauge and spacing of the metal wall studs in all wall types, or reference the location of that information. 2. Sheet CP1.1; Code Study: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise. 3. Sheet CP1.1; Code Plan: Typically the plan indicates new walls with darker line weights and a Wall Type reference. In the Agriculture Lab (Room 118), two walls do not have the darker line weights, but do have Wall Type 02A referenced. Please clarify. 4. Sheet CP1.1; Code Study (Summary): The Summary indicates two basement rooms will be renovated. Please reference in this Summary the sheet that indicates the basement renovation (the Code Plan on this sheet provides no renovation notes). 5. General: Please provide the Special Inspection Certificate with Parts A and B completed. 6. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 01/15/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/15/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Unless cups are available at an accessible location by the two drinking fountains, provide the number of drinking fountains that complies with the requirements of Section 1109.5.1, IBC 2012 and Section 410.2, IPC 2012. 2. Show how accommodation for the thermal expansion of the hot water system is being provided for the existing water heater. Reference: Section 607.3, IPC 2012. |
| 01/15/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations to verify that the proposed HVAC units together with the existing HVAC units are just sufficient to condition the building. Use the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson. 2. Provide structural calculations to verify that the roof framing is adequate to support the proposed mechanical units on the roof (e.g. point load as well as dead load). Provide structural details as required for any special framing revisions needed to support the units and frame the roof penetrations. Reference: Section 302.1, IMC 2012. 3. Provide structural calculations and details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2012. |
| 01/23/2019 | ELISA HAMBLIN | ZONING | REVIEW | Approved | |
| 01/29/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |