Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM09896
Parcel: 124050590

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T18CM09896
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2018 ANY ZONING REVIEW Active
12/20/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/20/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/20/2018 AHINES2 ENGINEERING REVIEW Passed
12/20/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. A service sink is required for this type of occupancy in accordance with IBC TABLE 2902.1
2. Please provide a hi/low drinking fountain or a point of use water distribution station in an accessible location. IBC TABLE 2902.1
3. Please identify the use of the room or space where access to the ADA restroom is provided, The rstroom must be accessible to all accupants.. SHT A-2.0
4. Show the fixed vertical grab bar for the water closet. ICC A117.1-2009
5. Provide plumbing fixture calculations for the office/mercantile use tenant space. IBC TABLE 2902.1
12/20/2018 ROBERT SHERRY WATER REVIEW Completed
12/20/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/20/2018 MASHFOR1 FIRE REVIEW Approved
12/20/2018 ANY COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active