Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2019 MARTIN BROWN FIRE REVIEW Approved
02/22/2019 ROBERT SHERRY WATER REVIEW Completed
03/04/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T18CM09810

1) Existing building is impacted by a FEMA flood Zone AH. Proposed tenant improvement is a substantial improvement as it exceeds 50% of the building value as defined by Chapter 26 of the Tucson City Code
2) The building will need to be floodproofed following FEMA regulations. See following link https://www.fema.gov/media-library/assets/documents/34270
3) The option exists to reduce the value of the improvements such that they do not exceed 50% of the building cost. Another option is to attempt an elevation certificate to potentially remove the structure from the floodplain
4) A floodplain use permit will be required

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007