Permit Number: T18CM09810
Parcel: 121050220

Address:
5548 E GRANT RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL TI

Permit Number - T18CM09810
Review Name: 3RD PARTY REVIEW - COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2019 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed
02/19/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T18CM09810

1) Existing building is impacted by a FEMA flood Zone AH. Proposed tenant improvement is a substantial improvement as it exceeds 50% of the building value as defined by Chapter 26 of the Tucson City Code
2) The building will need to be floodproofed following FEMA regulations. See following link https://www.fema.gov/media-library/assets/documents/34270
3) The option exists to reduce the value of the improvements such that they do not exceed 50% of the building cost. Another option is to attempt an elevation certificate to potentially remove the structure from the floodplain
4) A floodplain use permit will be required

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
02/19/2019 MARTIN BROWN FIRE REVIEW Reqs Change Please include fire sprinklers and fire alarm as deferred submittals on cover sheet.
Sheet A601 contains the door and frame schedule. Note 8 indicates panic hardware. Note 8 show up nowhere on the schedule. Please clearly indicate on schedule and floor plan locations of panic hardware.
02/19/2019 ROBERT SHERRY WATER REVIEW Reqs Change The plumbing floor plan on sheet P102 shows a new reduced pressure backflow prevention assembly located in an electrical room. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf. (Note that an existing backflow assembly is located along E. Edison Street, by the existing 2" water meter.)

Final Status

Task End Date Reviewer's Name Type of Review Description
02/19/2019 KROBLES1 OUT TO CUSTOMER Completed