Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM09638
Parcel: 12620001C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM09638
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2019 AMARTIN1 BUILDING-COMMERCIAL REVIEW Reqs Change Please provide written responses to all plan review comments:
1. Sheets S3, S5 and S7 item #3 all make reference to STEEL COLUMN PER TABLE THIS SHEET; the referenced table is not shown on the sheets. Please provide referenced tables. IBC 107.2.1
2. Sheets S3, S4 and S7 PANEL TEE SECTION drawings. Provide the EQ dimensions from Nodes 3 and 4 to the centerline of column and drilled pier so that the shade structures can be referenced back to the Steel Frame Model Info and Base Reactions contained in the Structural Calculations. IBC 107.2.1.
3. The strucural members shown on the Steel Frame Model Info and Base Reactions do not match the sizes of framimg members on the structural plans. Indicate the specific shade structure on the plans for each Steel Frame Mode Info and Base Reaction drawing in the structural calculations.
01/04/2019 AMARTIN1 ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/10/2019 AMARTIN1 OUT TO CUSTOMER Completed