Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM09638
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2019 | AMARTIN1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please provide written responses to all plan review comments: 1. Sheets S3, S5 and S7 item #3 all make reference to STEEL COLUMN PER TABLE THIS SHEET; the referenced table is not shown on the sheets. Please provide referenced tables. IBC 107.2.1 2. Sheets S3, S4 and S7 PANEL TEE SECTION drawings. Provide the EQ dimensions from Nodes 3 and 4 to the centerline of column and drilled pier so that the shade structures can be referenced back to the Steel Frame Model Info and Base Reactions contained in the Structural Calculations. IBC 107.2.1. 3. The strucural members shown on the Steel Frame Model Info and Base Reactions do not match the sizes of framimg members on the structural plans. Indicate the specific shade structure on the plans for each Steel Frame Mode Info and Base Reaction drawing in the structural calculations. |
| 01/04/2019 | AMARTIN1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/10/2019 | AMARTIN1 | OUT TO CUSTOMER | Completed |