Permit Number: T18CM09539
Parcel: 112052790

Address:
2333 E GLENN ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM09539
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Indicate the conduit sizes for the secondary service conductors in the Fault Current tables or the Single Line Diagram.
2. The common grounding electrode system is not completely connected to all the services. Plan sheet E-601.
Ref; 2012 IBC sec 107.2.1, 2011 NEC 250.