Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM09539
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/09/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Indicate the conduit sizes for the secondary service conductors in the Fault Current tables or the Single Line Diagram. 2. The common grounding electrode system is not completely connected to all the services. Plan sheet E-601. Ref; 2012 IBC sec 107.2.1, 2011 NEC 250. |