Permit Number: T18CM09539
Parcel: 112052790

Address:
2333 E GLENN ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM09539
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/17/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1 Any new or extended branch circuits as a result of relocating sub-panels, or installing additional new circuits for convenience or equipment will require updating to Arc Fault protection of that branch circuit. Where applicable. Please include a notation on the plans to address this. NEC 210.12B
#2 Ref; Plan Sheets E601, E701. Keyed note 3, 4, & 12, on plan sheet E601 calls for WAVE-RIB as a raceway for the secondary service conductors. Plan Sheet E701 FAULT CURRENT tables call out PVC. Please clarify. Be advised that the NEC does not recognize WAVE-RIB as a listed raceway.
#3 The grounding electrode system is required to be common for the multiple services, Per NEC 250.58. Please provide for this on the plans.
Ref; 2012 IBC sec 107.2.1, 2011 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/03/2019 QJONES1 APPROVAL SHELF Completed
01/03/2019 QJONES1 OUT TO CUSTOMER Completed
01/03/2019 QJONES1 REJECT SHELF Completed