Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM09539
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/17/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1 Any new or extended branch circuits as a result of relocating sub-panels, or installing additional new circuits for convenience or equipment will require updating to Arc Fault protection of that branch circuit. Where applicable. Please include a notation on the plans to address this. NEC 210.12B #2 Ref; Plan Sheets E601, E701. Keyed note 3, 4, & 12, on plan sheet E601 calls for WAVE-RIB as a raceway for the secondary service conductors. Plan Sheet E701 FAULT CURRENT tables call out PVC. Please clarify. Be advised that the NEC does not recognize WAVE-RIB as a listed raceway. #3 The grounding electrode system is required to be common for the multiple services, Per NEC 250.58. Please provide for this on the plans. Ref; 2012 IBC sec 107.2.1, 2011 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/03/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 01/03/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 01/03/2019 | QJONES1 | REJECT SHELF | Completed |