Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM09133
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/05/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G2.0; Construction Keynotes: Several notes reference Cemrock items. Please make those drawings/details/plans available for review. 2. Sheets A1.0, A2.0, A3.0, and A4.0: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the Keynotes. 3. Sheet A1.0; Demolition Keynotes: Note 3 indicates a shaded area for the concrete slab to be removed. The shaded area does not show up on the plan. Please revise. 4. Sheet A5.0: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the Keynotes and Notes. 5. Sheet S1.0 (Column Schedule); Sheet S3.0 (Detail 101): The Column Schedule references Detail 101 for the column base connection, but Detail 101 does not indicate the size of the base plate or the anchor bolts. Please provide. 6. Structural Calculations; Cover Sheet: The City of Tucson requires a bottom of footing depth of 18" below the exterior grade or finish floor slab to obtain an allowable soil bearing value of 1500 PSF. Please revise the calculation cover sheet, and add the depth requirement to the General Structural Note 8 on Sheet S1.0. 7. General: Please provide a Special Inspection Certificate with Parts A and B completed. 8. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
12/11/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
12/13/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The specified freeze-proof yard hydrant uses a below-grade stop-and-waste valve. This is prohibited unless an approved upstream backflow prevention device is use to protect the upstream potable water source and the downstream outlets are identified with signs that read, "Caution, Nonpotable water, Do Not Drink. Reference: Section 608.7, IPC 2012. 2. A vent for a combination waste and vent system shall rise vertically to at least 6" above the flood rims of the fixtures it protects prior to running horizontally. Note: the required dry vent for a combination waste and vent system may connect to the system at any point. Reference: Section 915.2.2, IPC 2012. |
12/13/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance for the alterations to the building envelope based on the current code. Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012. 2. "Pet" areas are required to have 0.9 CFM of exhaust per square foot. Provide the sequence of operation for the two exhaust fans and show ho. Reference: Section 403.3, IMC 2012. |
12/13/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
12/17/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/19/2018 | KROBLES1 | ZONING | REVIEW | Needs Review | APPLICANT DECIDED TO WALK PLANS THREW |