Permit Number: T18CM08711
Parcel: 10503002B

Address:
60 W STONE LP

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM08711
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide the following information on the plan.
(a) As well as the lighting area, indicate the Option used.
(b) Indicate lamp color temperature. Sec 402.1
(c) How did you calc the "Allowable Full Cut- Off Lumens"?
(d) Indicate the quantity of each luminaire and correlate with the lumen calcs.
Ref; 2012 Tucson/Pima County Outdoor Lighting Code.