Permit Number: T18CM08709
Parcel: 117142140

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T18CM08709
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 5; Sheet A0.2; Exiting Plan: The new Note 1 indicates Table 1015.1 for a B Occupancy Classification with an occupant load of 74 requires only one exit. The maximum occupant load listed in that Table for one exit only is 49. Please revise.
2. Previous Comment 5; Sheet A0.2; Exiting Plan: The new Note 2 indicates the diagonal across the Program Space is 44 feet. Please indicate on the Exiting Plan the Program Space location. In addition, indicate the distance between the exits on the same plan.
3. Previous Comment 7; Sheet A1.0; Site Plan: The new Separation Notes 1 and 2 indicate buildings separated by more than 10 feet do not require fire resistance rated adjacent walls. Per the IBC Section 202, the fire separation distance is measured from one building face to: (1) the closest interiior lot line; (2) the centerline of a street, alley, or public way; (3) to an imaginary line between two buildings on the property. Using (3), the actual separation between two building walls is 20 feet (each wall to the imaginary line 10 feet away per Table 602). Please revisit the required exterior wall fire resistance rating with this information.
4. Previous Comment 8; Sheet A2.0; Floor Plan: The structural detail tag in Restroom 105 was not revised.
5. Previous Comment 11; Sheet A2.0; Floor Plan: The tag for the Enlarged Bar Plan (1/A2.2) was not indicated on the plan.
6. Previous Comment 15; Sheet A2.4; Accessible Mounting Heights: Please remove the ADAAG references in Notes 1, 2, 3, and 5, and in General Notes 6.
7. Previous Comment 16; Sheet A2.4; Accessible Mounting Heights: Please add the rear wall grab bar per the ICC/ANSI Figure 604.5.2.
8. Previous Comment 24; General: Please add Site Preparation to the Special Inspection Certificate.
9. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
01/17/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. An approved development plan is not a substitute for a building permit to install site utilities (e.g. water service to the building, building sewer, etc.). Provide a site plan showing the installation of the water service to the building and the installation of the building sewer. Reference: Sections 104.2 and 107.2.1, IBC 2012. [Initial comment: Show where the water meter and backflow preventer are located and show the route of the water service pipe. Reference: Section 107.2.1, IBC 2012.]
2. An approved development plan is not a substitute for a building permit to install site utilities (e.g. water service to the building, building sewer, etc.). Provide a site plan showing the installation of the water service to the building and the installation of the building sewer. Reference: Sections 104.2 and 107.2.1, IBC 2012. [Initial comment: Provide the site drawing noted on sheet P1.0 that shows the size, route slope, and all cleanouts in the building sewer. Show where the building sewer connects to the public sewer. Reference: Section 107.2.1, IBC 2012.]
3. The horizontal drain for the water closet and lavatory for room 105 is still shown as 2" on the plumbing waste floor plan. [Initial comment: Correct the size of the horizontal drain for the water closet and lavatory in room 105. It is shown as 3" in the waste and vent isometric but 2" in the plumbing waste floor plan.]
4. Section 701.7, IPC 2012 requires any wastewater be cooled to less than 140-degrees Fahrenheit prior to disposal. The use of cast iron is not an option provided by the IPC. Dishwasher manufacturers typically provide tempering kits for their products. [Initial comment: Verify that the discharge from the dishwashers (kitchen equipment numbers 7 and 65) will be 140 degrees Fahrenheit or less. Reference: Section701.7, IPC 2012.]
5. Revise the roof drain calculations to include area of the top surface of the parapets and the effect of any vertical walls that can divert rainfall onto the roof. Secondary drainage provides protection for the roof, not the scupper box. If secondary drainage is not to be provided for the roof, provide structural calculations to show that the roof is capable of supporting the additional rain load caused by the primary roof drains being blocked. Note that scuppers are weirs and their size is not determined using Table 1106.2(2), IPC 2012. Scuppers that "daylight" onto another roof still need a secondary drain. The 2012 IPC does not address the use of holes in scupper boxes; secondary drainage is independent from primary drainage and discharges to a separate point. The secondary drainage has the same capacity as the primary drainage. Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012. [Initial comment: Provide roof drainage calculations. Provide overflow protection for the roof. The scuppers require secondary roof drainage and as depicted in detail 4/A4.0, the gutter will also require secondary drainage. Reference: Sections 1101, 1106 and 1108, IPC 2012.]
01/18/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Specify the R-value of the continuous roof insulation on the drawing (shown as R-38 in the COMcheck envelope component description). [Initial comment: Demonstrate energy code compliance for the building envelope using calculations based on the current code (i.e. provide COMcheck Envelope Compliance Certificate). Coordinate the response to Section C406 with the mechanical and electrical designs, Reference: Sections C101.3, C101.5, C103.2, C303, C401.2, and C406International Energy Conservation Code 2012.]
01/29/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM08709 - The Downtown Clifton - New Building/Restaurant-Bar
Building Plan Review (2nd Review)
485 S. Stone Avenue

TRANSMITTAL DATE: January 29, 2019

DUE DATE: January 28, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Zoning has reviewed the Building plans for compliance with the revised and approved development package DP16-0238. While the building footprint is consistent with the DP as it relates to the zoning review purview Building footprint, Height, square footage, site conditions etc., zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage, location, and the building package site plan to ensure consistency with the DP.

3. COMMENT: The previous building plans were approved and signed by Carolyn Laurie for the Design Professional. The final building plans will have to be approved, re-stamped and signed by Carolyn Laurie for the Design Professional once the building plans have been approved by all plans reviewers.

4. COMMENT: Once the plans have been reviewed and approved by the PDSD Commercial Plan Reviewers and the Design Professional, and zoning has verified continued consistency with the DP, the building plans can be approved by zoning.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Building Plans
01/30/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T18CM08709

1) Once all commercial review comments have been address engineering can approve the plans over the counter. Call or Email to Schedule once all oustanding comments are addressed and a new work flow has been opened

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007