Review Details: WALK THRU - RES
Permit Number - T18CM08679
Review Name: WALK THRU - RES
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/30/2018 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: T18CM08679 42 E. Bilby Road Enclose carport to room & interior remodel TRANSMITTAL: October 30, 2018 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-2 zone (UDC 4.7.9). Multi-family residential is a permitted use in this zone (Table 4.8-2). See Use Specific Standards 4.9.7.B.6, .9 & .10. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Based on a wall height of less than 9'-0" the required perimeter yard setback from the enclosed carport is 6'-0", proposed setback is 5'-0" |
| 10/30/2018 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 12/11/2018 | QJONES1 | BUILDING-RESIDENTIAL | REVIEW | Needs Review |