Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM07852
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/03/2018 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 10/03/2018 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
| 10/04/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/04/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 10/04/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/04/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/04/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/05/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/05/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/12/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
| 12/12/2018 | AVAUGHN1 | REJECT SHELF | Completed |
| 10/05/2018 | AVAUGHN1 | APPROVAL SHELF | Completed |